We continue on from part 1 in this solar cable for a 1 MW ground mount system series. Parallel strings, voltage drop considerations and allowing for errors when calculating your runs are all examined.
Things to think about.What about voltage drop calculations? What percentage increase should I allow for bends? What about mistakes? Should we parallel the strings instead?
The assumptions:
In addition looking at:
Per row there are 8 x strings of 20 x 400 watt panels per string so row length is approximately 85 metres wide.
There are 20 rows, total distance, North South with spacing is 142 metres which includes the 4 metre North and 4 metre South perimeter roads.
Distance from row 1 to row 20 is approximately 133 metres ( excluding perimeter access roads North South, 4 metres each)
We have all these cable runs resulting in more than 27,000 metres of cable in all and there are some questions to ask:
We need to maintain less than 3% on the DC volt drop side according to CEC recommendations.
The longest cable run row 1 is approximately 166 metres and we will assume that the Vmpp ( Voltage at Maximum Power Point) for this string is 800 volts.
The short circuit current of the panels in question are 10A so what is the volt drop using 4mm2 DC cable?
Volt drop using 4mm2 over 166 metres
Using cable resistance Rc values from Table 35 in AS/NZS 3008
There is a total Vdrop of 18.63
As a percentage this 2.33%
So worst case scenario 4 mm2 cable is OK
If we used 6 mm2 the Vdrop is 1.56%
Calculation is (10A x 166L metres x 2 x 3.75R)/1000 then convert to a percentage by dividing into the 800 Vmpp
Which are we to choose?
https://www.jcalc.net/voltage-drop-calculator-as3008
Is 4 mm2 cable really OK for this run?
Using 4mm2 cable we have:
*we are assuming inverters have their own built in DC isolators
What if we decide to parallel the strings?
What cable satisfies our Volt drop requirements?
But we have to add the cable run to the centre of the row!
Let’s say we use 4 mm2 for this 31 - 32 metre approximate run and we are carrying a current of only 10A and the Volt drop % is 0.43%
The sum of both volt drops is precariously close to 3%.
Probably best to use 6 mm2 also on this run @ 0.29%.
With a design that does not parallel can only use a minimum 4 mm2 but if we parallel, the minimum we can use is 6 mm2 on the longest runs.
Paralleling 2 x strings saves on the number of DC isolators used and it also saves on labour time, cables, less connections, less work.
From a cost perspective our design could use both 4 and 6 mm2!
6 mm2 is the winner based on this approach
But this is not the full story!!
In part 3 we go into more detail.
Large solar projects, both ground mount and roof mount require a considerable amount of DC cable so there is definitely a need for a process and procedure that allows accurate calculations of these runs.
This is part two of a three part series.
If you’d like to see more of what Greenwood Solutions get up to in the real world of renewable energy, solar, battery storage and grid protection check out the following pages:
https://www.greenwoodsolutions.com.au/industry
https://www.greenwoodsolutions.com.au/commercial
https://www.greenwoodsolutions.com.au/commercial/customer-stories
https://www.greenwoodsolutions.com.au/news